by Clay Hile, Parameter
Generation & Control,
Inc.
Providing a specified humidity and temperature for testing or
process control can be difficult and reaching the TAPPI (Technical
Association of the Pulp and Paper Industry) prescribed testing
atmosphere of 23°C +1°/50% RH ±2% can be close
to impossible. Even TAPPI acknowledges, “the required relative
humidity and temperature are difficult to achieve, and therefore
careful attention must be given to the design, evaluation, and
maintenance of the standard room” (TAPPI T 402 om-88 1988).
The ability to produce a recording, display, or printout that
is within a specified tolerance can be a challenge, but this
is only one of three parameters that should be considered. The
display or recording is typically connected to one sensor and
specifically monitors what is happening at that one location
in your room, chamber, or section of ductwork. The information
from this sensor indicates the control constancy of the conditioner/controller
system but it does not provide information on the conditions
in various areas of the conditioned space.
In order to fully comprehend the true conditions for the test
or process environment the following parameters must be properly
considered:
To obtain the true required conditions, a chamber or room must
be designed with all three aspects of condition deviation in
mind.
Single Point Constancy (control)
Within this category, account must be taken for conditioner/controller
cycling, day/night and seasonal cycling, and sudden load
changes (machinery or turning lights on or off, door openings).
This
portion is dependent on the capability of conditioning
equipment and controls.
Short-term conditioner control can be assessed when there are
no load changes within the controlled area. Conditioner cycling
includes refrigeration, heaters, and humidity/dehumidification
cycles. Day/night, seasonal, and load cycling all involve an
increase or decrease in sensible and latent loads and affect
the long-term stability of the conditioned area. Ambient driven
change can be minimized with appropriate insulation, good vapor
barrier, and proper handling of make-up air.
A conditioning system must be designed to handle the maximum
anticipated latent and sensible loads. The source of most latent
loads comes from people, leakage, sinks, and fresh air make-up.
Sensible loads come from lighting, equipment, people, leakage,
and make-up air. The system must be able to stay in control while
the heat loads vary throughout daily and seasonable cycles.
Precise air temperature control is required for close relative
humidity control. If moisture content stays constant at a 12°C
dew point, but the air temperature is cycling ±1.0°C,
the relative humidity is fluctuating between 47% and 53%. A small ±0.2°C
air temperature cycle will cause a relative humidity cycle of
more that 0.5% (ASHRAE 1993).
Sensor Accuracy
Temperature
sensors are typically much more accurate and easier to calibrate
than humidity sensors. Since it is fairly easy to
obtain a ±0.1°C accuracy for the temperature sensor,
humidity measurement is the primary concern in this area.
Most humidity sensors on the market today have an accuracy specification
of +1%. This is the best that can be expected from a new sensor
that is operating under moderate conditions. When choosing a
humidity sensor, the accuracy specification should be checked
over the entire range of expected operation. For example, if
there are plans to cycle temperature and humidity, ensure that
the humidity sensor is temperature compensated for the anticipated
cycling range and that its accuracy does not shift with temperature.
Most humidity sensors lose accuracy above 85% to 90% relative
humidity.
Be sure to calibrate the sensors routinely for humidity sensors
will drift over time. Calibration intervals will vary based on
the type of sensor and the conditions of operation (temp. humidity
range, cleanliness of atmosphere, concentration of various chemicals).
Typically a one-year calibration interval is sufficient. Confirm
that the calibration covers your operating range and is traceable
to N.I.S.T. (National Institute of Science & Technology)
and ask for documentation on the calibration instrumentation.
Traceability means that the instrument has been calibrated against
a primary or transfer standard. Most sensors are supplied with
a calibration report showing the accuracy at the time of manufacture,
which does not truly reflect the way the instrument will perform
in the field (Wiederhold 1997). The accuracy of the controller
or adjustments made in the circuitry down stream of the sensor
can affect the accuracy of the readout. One way to avoid these
errors are to field calibrate the control sensor with a transfer
standard while the system is in operation.
Uniformity
Uniformity deals with the point-to-point differences of temperature
and humidity across an entire conditioned area. Some of the
major items that affect uniformity include: total heat (sensible
and latent) load, load location, control sensor location, air
distribution, volume of air moved, proper insulation and vapor
barriers.
Total heat load (lights, equipment, people, infiltration through
walls and ductwork, and make-up air) is the most important item
affecting uniformity. If there were absolutely no load within
the conditioned space, then uniformity would be easily handled.
A 12’ x 10’ x 10’ room (1,200 cubic feet) with
equipment, moving 600 CFM (30 air changes per hour) and a 3,000
BTU (880 watts) load has a temperature difference from supply
to return of 2.6°C. If air is supplied at 23°C/50% RH
and assuming there is no change in moisture content, than air
is returned at 25.6°C/43% RH. Increasing airflow, or decreasing
load can reduce this difference.
3000 BTU (880 watt) Internal Load
| Supply Air |
Air Changes per Hour |
Return Air |
| 23°C/50% RH |
15 (300 CFM) |
27.8°C/37% RH |
| 23°C/50% RH |
30 (600 CFM) |
25.6°C/43% RH |
| 23°C/50% RH |
45 (900 CFM) |
24.5°C/45% RH |
| 23°C/50% RH |
60 (1200 CFM) |
23.9°C/48% RH |
The total volume of air moved is an important consideration
when designing the distribution system and minimizing the effects
of heat loads. Depending on the processes and internal load,
25 to 45 air changes per hour is a good target. TAPPI recommends
15 to 30 air changes per hour (TAPPI TIS 018-7 1982), and that
could still be insufficient depending on the amount of internal
load.
Load location is also an important factor. If possible, it is
best to locate loads as close to a return duct as possible to
avoid affecting the rest of the conditioned space. Load location
should also influence the location of the control sensors. Control
sensors should not be located down stream of major load producers
or in the return duct.
Air distribution should be uniform across the conditioned space.
Typically, ceiling supplies and returns that pick up near the
floor around the periphery of the conditioned space are recommended
(TAPPI TIS 018-7 1982). A design with both ceiling supplies and
returns should be avoided.
Applying the proper insulation and vapor barriers to the room
and ductwork are very important depending on the conditions in
the adjacent spaces. The importance of proper ductwork cannot
be over emphasized. Due to the increased air velocity in the
duct, the effect of a hole in the ductwork is much greater than
the same size hole in the chamber. Avoiding outside walls, windows,
and drop ceilings are also helpful.
Conclusion
Obtaining your specified
temperature and humidity conditions can be a difficult task,
but not an impossible one. If
all the factors that affect environmental conditions are
taken
into consideration, the goal is certainly achievable.
Some of the key points to remember are:
If the above items are given serious consideration, the problems
of providing a conditioned space with precise temperature and
humidity specification will be much more easily resolved.
References
ASHRAE (American Society of Heating, Refrigeration
and Air Conditioning Engineers) Handbook – Fundamentals,
1993, Chapter 6 - Psychrometrics
TAPPI (Technical Association of the Pulp and Paper Industry)
TIS 018-7, “Paper Test Rooms: Design Considerations”,
1982
TAPPI T402 om-88, “Standard Conditioning and Testing Atmospheres
for Paper, Board, Pulp Handsheets, and Related Products”,
1988
Wiederhold, Pieter R., “Water Vapor Measurement – Methods
and Instrumentation”, 1997, Chapter 10 - Calibration
Humidity Control Chamber HOME > Humidity
and Temperature Conditions < you are here