To obtain the true required conditions, a chamber or room must
be designed with all three aspects of condition deviation in
mind.
Single Point Constancy (control)
This is the amount of cycling or deviation from
set point one would expect from the control sensor’s location.
Within this category, account must be taken for conditioner/controller
cycling, day/night and seasonal cycling, and sudden load
changes
(machinery or lights turning on or off, door openings,
etc.). This aspect is dependent on the capability of the conditioning
equipment and its controls.
Short-term conditioner control can be assessed when there are
no load changes within the controlled area. Conditioner cycling
includes refrigeration, heaters, and humidity/dehumidification
cycles. Day/night, seasonal, and load cycling all involve an
increase or decrease in sensible and latent loads that affects
the long-term stability of the conditioned area. Ambient-driven
change can be minimized with appropriate insulation and an adequate
vapor barrier.
A conditioning system must be designed to handle the maximum
anticipated latent and sensible loads. The source of most latent
loads comes from, leakage, product, and door openings. Sensible
loads come from lighting, equipment, leakage, and door openings.
The system must be able to maintain control while the heat loads
vary throughout daily and seasonal cycles.
Because relative humidity is temperature dependent, precise
air temperature control is required for close relative humidity
control. If moisture content stays constant at a 16.7°C dew
point, but the air temperature is cycling ±1.0°C at
25°, the relative humidity is fluctuating between 56.5% and
63.7%. A small ±0.2°C air temperature cycle will cause
a relative humidity cycle of more that 0.5% (ASHRAE 1993).
Uniformity
Uniformity deals with the point-to-point differences of temperature
and humidity across an entire conditioned area. Some of the
major influences affecting uniformity include: total heat load
(sensible and latent), load location, control sensor location,
air distribution, volume of air exchanged, proper insulation
and vapor barriers.
Total heat load (lights, equipment, people, and gain or loss
through walls and ductwork) is the most important item affecting
uniformity. If there were absolutely no load within the conditioned
space, then uniformity would be easily handled, however this
is not practical. For example: a 12’ x 10’ x 10’ room
(1,200 cubic feet) with equipment, moving 600 CFM (30 air changes
per hour) and a 3,000 BTU (880 watts) load has a temperature
difference from supply to return of 2.6°C. If air is supplied
at 25°C/60% RH and assuming there is no change in moisture
content, then air is returned at 27.6°C/51% RH. Increasing
total airflow or decreasing load can reduce this difference.
At higher humidities, this same change in air temperature has
a greater effect on the relative humidity.
3000 BTU (880 watt) Internal Load
| Supply Air |
Air Changes per Hour |
Return Air |
| 25°C/60% RH |
15 (300 CFM) |
30.2°C/44% RH |
| 23°C/50% RH |
30 (600 CFM) |
27.6°C/51% RH |
| 23°C/50% RH |
45 (900 CFM) |
26.7°C/54% RH |
| 23°C/50% RH |
60 (1200 CFM) |
26.3°C/56% RH |
The total volume of air exchanged is an important consideration
when designing the distribution system and minimizing the effects
of heat loads. Depending on the processes and internal load,
25 to 45 air changes per hour is a good target.
Load placement is also an important factor. If possible, it
is best to locate loads as close to a return duct as possible
to avoid disturbing the rest of the conditioned space. Load location
should also influence the placement of the control sensors. Control
sensors should not be located down stream of major load producers
or in the return duct(s).
Air distribution should be uniform across the conditioned space.
Typically, ceiling supplies and returns that pick up near the
floor and around the periphery of the conditioned space are recommended
(TAPPI TIS 018-7 1982). A design with both ceiling supplies and
returns should be avoided.
Applying the proper insulation and vapor barriers to the room
and ductwork are very important depending on the conditions in
the adjacent spaces. The importance of proper ductwork cannot
be over emphasized. Due to the increased air velocity in the
duct, the effect of a hole/leak in the ductwork is much greater
than the same size hole in the chamber. Avoiding outside walls,
windows, and drop-ceilings are also helpful as these typically
are greater heat loads than interior spaces.
Sensor Accuracy
There are both temperature and humidity sensors
employed that need to be considered. Temperature sensors are
typically
far more accurate and generally easier to calibrate than humidity
sensors. Using standard practices, one can typically obtain
a ±0.1°C
accuracy for the temperature sensor. Humidity measurement
therefore becomes the primary area of concern.
Most humidity sensors on the market today have a claimed accuracy
of +1% throughout a slightly narrowed range (i.e.: 20-80%RH).
This is the best that one could expect from a new sensor, operating
under moderate conditions. When choosing a humidity sensor, the
accuracy specification must be validated over the entire expected
range of operation. For example, if procedure calls to cycle
temperature and humidity, one must ensure that the humidity sensor
is properly temperature-compensated for the anticipated cycling
range and that its accuracy does not shift as a function of temperature.
Most humidity sensors lose accuracy above 80% relative humidity.
Relative humidity sensors must be calibrated regularly as they
will drift over time. Calibration intervals will vary based on
the type of sensor and the conditions of operation (temp. humidity
range, cleanliness of atmosphere, concentration of various chemicals,
etc). Typically, a one-year calibration interval is sufficient
and should be considered the maximum. Specific intervals will
be dictated by the application and it is best to start conservatively
(i.e.: 6 months) and adjust later as appropriate. Confirm that
the sensor calibration covers your operating range and is traceable
to N.I.S.T. with supporting documentation on the calibration
of the instrumentation.
Traceability means that the instrument has been calibrated against
a primary or transfer standard. Most sensors are supplied with
a calibration report (Certificate of Calibration) showing the
accuracy at the time of manufacture, which does not truly reflect
the way the instrument will perform in the field (Wiederhold
1997). The accuracy of the controller or adjustments made in
the circuitry down stream of the sensor can affect the accuracy
of the readout. One-way to avoid these errors is to field (in
situ) calibrate the control sensor with a transfer standard while
the system is in operation. This would be done using a suitable
transfer standard such as a chilled mirror hygrometer.
Conclusion
Obtaining your specified temperature and humidity conditions
can be a difficult task, but not an impossible one. If all
the factors that affect environmental conditions are taken
into consideration, the goal is certainly achievable. Some
of the key points to remember are:
If the above items are addressed, most of the problems associated
with providing a conditioned space with precise temperature and
humidity specifications will be eliminated and compliance with
ICH should be met.
References
ASHRAE (American Society of Heating, Refrigeration
and Air Conditioning Engineers) Handbook – Fundamentals,
1993, Chapter 6 - Psychrometrics
TAPPI (Technical Association of the Pulp and Paper Industry)
TIS 018-7, “Paper Test Rooms: Design Considerations”,
1982
TAPPI T402 om-88, “Standard Conditioning and Testing Atmospheres
for Paper, Board, Pulp Handsheets, and Related Products”,
1988
Wiederhold, Pieter R., “Water Vapor Measurement – Methods
and Instrumentation”, 1997, Chapter 10 - Calibration