Conditioning Units

calibration chambers
humidity control chamber
Home Catalog Products How It Works Where It Works Support References Humidity Links Contact
United States/Great Britain Spanish Korean Chinese Vietnamese International Distributors

Calibration Chambers

Controlled Spaces from 4.5 to 1000 Cubic Feet

humidity chambers
4.5 cubic foot unit (shown with
optional base cabinet and recorder)
humidity and temperature control
30 cubic foot unit
walk in chambers 9530 & 9540 PDF

temperature chambers
10’ x 10’ room with 700 CFM
conditioner

FEATURES

  1. Precise chamber control
  2. Rack-mounted hygrometer
  3. Hygrometer utilizes primary measurement technique
  4. Long proven and unsurpassed humidity control system
  5. Highly accurate NIST traceable sensor
  6. Sensing system discriminates between dew and contaminants

BENEFITS

  1. Reduces uncertainty
  2. Easy to provide NIST recertification
  3. Proven methodology
  4. Extremely stable and uniform environment
  5. Reliable data
  6. Worry-free

Precise Control with Chilled Mirror Accuracy

PGC and EdgeTech provide large volume calibration chambers that combine the quality and durability of the PGC line with the proven
technology of the EdgeTech hygrometer. These chambers are utilized for large volume calibrations, and testing/quality control applications requiring humidity and temperature control within very narrow tolerances.

When specific conditions are required, accuracy, constancy, and uniformity of an atmosphere must be considered. EdgeTech provides an accurate humidity and temperature measurement, while PGC maintains a precise control constancy and chamber uniformity.

Reach-in systems are equipped with a window in the outer door, a clear inner door, an iris opening (for making adjustments without an inner door opening), and a cable port.

Walk-ins can be custom sized and arranged with various shelving configurations. Cable ports, windows, and HEPA filtration are also available.

All units are equipped with a SmartPad controller which includes automatic ramping, alarms, and a digital communications port.

Performance Curve:

test chambers


Specifications:

4.5 Cubic Foot Model Series 9540 (EC4)

Relative Humidity Control: ±0.3%
Relative Humidity Uniformity: 0.5%*
Dew Point Accuracy: ±0.2°C
Relative Humidity Range: 10 to 95%

(See chart above)
*at 25ºC/50% RH

Temperature Control: ±0.2°C
Temperature Uniformity: ±0.3°C**
Temperature Accuracy: ±0.2°C
Temperature Range: 7 to 85°C

Minus 10 option available
**within 15 degrees of ambient

Dimensions

Internal: 18"w x 18"d x 24"h
External: 41"w x 29"d x 46"h*

*75"h with optional base cabinet

Utilities

  • 115 v, 16 FLA, 1 phase, 60 Hz (Available
    in other voltages at 50 Hz)
  • Water: 2 gallons per day maximum (can
    be manually refilled without hard piping)
  • Drain: Hard piped or evaporation pan

Weight

600 lbs.

Shipping Weight

800 lbs. (domestic)

Engineering drawings available on request

Specifications:

30 Cubic Foot Model Series 9530 (EC30)

Relative Humidity Control: ±0.3%
Relative Humidity Uniformity: 0.5%*
Dew Point Accuracy: ±0.2°C
Relative Humidity Range: 10 to 95%

(See chart above)
*at 25ºC/50% RH

Temperature Control: ±0.2°C
Temperature Uniformity: ±0.3°C**
Temperature Accuracy: ±0.2°C
Temperature Range: 7 to 85°C

Minus 10 option available
**within 15 degrees of ambient

Dimensions

Internal: 34-1/2"w x 28-1/2"d x 53"h
External: 53-1/2"w x 42-1/2"d* x 79"h

*36"d without hardware

Utilities

  • 230 v, 15 FLA, 1 phase, 60 Hz (Available
    in other voltages at 50 Hz)
  • Water: 3 gallons per day maximum (can
    be manually refilled without hard piping)
  • Drain: Hard piped or evaporation pan

Weight

1150 lbs.

Shipping Weight

1400 lbs. (domestic)

Engineering drawings available on request

Specifications:

Rooms

Relative Humidity Control: ±0.3%
Relative Humidity Uniformity: ±0.5%*
Dew Point Accuracy: ±0.2°C
Relative Humidity Range: 10 to 90%

(See chart above)
*at 25ºC/50% RH

Temperature Control: ±0.2°C
Temperature Uniformity: ±0.3°C**
Temperature Accuracy: ±0.2°C
Temperature Range: 7 to 60°C

Below freezing available
**within 15 degrees of ambient

Dimensions

Rooms configured in 1 foot increments

Utilities

Varies on room size and condition range.
Call for specific application.


Humidity Control Chamber HOME > Environmental Test Chambers < you are here


Home | About Us | Our Products | How It Works
Where It Works
| Support | Humidity Control Chambers
Resources | Links | Sitemap | Contact Us

Parameter Generation & Control
Parameter Generation and Control
PO Box 129 | Black Mountain, NC 28711
828-669-8717 | 1-800-438-5494
sales@humiditycontrol.com
Copyright © 1977 - Parameter Generation & Control, All rights reserved


conditioning units - environmental test chambers